VKM 160*
Inline centrifugal fan. Maximum capacity - 580 m3/h.
Voltage / frequency: |
Products in this series (41)
* Compliant to the ErP-regulation (EC) 327/2011, the power consumption at optimum efficiency is < 125W.
Parameter | Value | Unit | |
---|---|---|---|
Phase | 1 | ˜ | |
Frequency | 50 / 60 | Hz | |
Voltage | 220-240 | V | |
Current | 0.43 / 0.52 | A | |
Power consumption | 98 / 119 | W | |
Maximum air capacity | 555 / 580 326,895 / 341,62 154,29 / 161,24 0,15429 / 0,16124 9268,5 / 9686 | m³/h CFM l/s m³/s l/m | |
RPM | 2705 / 2855 | min -1 | |
Noise level at 3 m | 47 / 48 | [dBA] | |
Maximum transported air temperature | -25 +55 / -25 +50 | оC | |
Protection rating | IP X4 | class | |
Weight | 3.65 | kg | |
Spigot size | 160 | mm | |
High-powered motor | no | ||
Low-noise design | no | ||
Energy-efficient motor with low energy demand | no | ||
SEC Class | B |
Sizes | ØD | B1 | ØD1 | B | L | L1 | L2 | L3 |
---|---|---|---|---|---|---|---|---|
mm | 159 | 317 | 304 | 357 | 220 | 25 | 25 | 30 |
Phohe
Customer service.
+380 44 406 36 25
Online form
Send a message center customer support.
- Selection method:
- Performance:
- Pressure:
Duty point
- Performance:- -
- Pressure:- -
- Power:- -
- Recovery Efficiency:- -
Sound-power level | Octave-frequency band [Hz] | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to inlet | dBA | 68 | 41 | 65 | 64 | 63 | 61 | 57 | 47 | 35 | ||||||||||
LwA to outlet | dBA | 70 | 47 | 67 | 68 | 66 | 64 | 60 | 51 | 41 | ||||||||||
LwA to environment | dBA | 60 | 40 | 61 | 55 | 39 | 18 | 16 | 28 | 22 |