VENTS - manufacture of ventilation and air conditioning systems
VS 710-6D
Inline centrifugal sound- and heat-insulated duct fans with back-curved impeller blades. Maximum capacity - 15830 m3/h. |
Technical parameters
Parameter | Value | Unit | |
---|---|---|---|
Phase | 3 | ˜ | |
Voltage | 400 | V | |
Frequency | 50 | Hz | |
Current | 3.9 | A | |
Power consumption | 2000 | W | |
RPM | 890 | min -1 | |
Noise level at 3 m | 59 | [dBA] | |
Maximum transported air temperature | -20 +40 | оC | |
Protection rating | IP X4 | class | |
Maximum air flow capacity at cross directed | 15830 | m³/h | |
Maximal air flow capacity at straight directed | 14880 | m³/h | |
Weight | 136 | kg | |
Spigot size | 710 | mm | |
Number of poles | 6 |
Diagrams
Sound-power level | Octave-frequency band [Hz] | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to inlet | dBA | 79 | 64 | 66 | 71 | 74 | 72 | 71 | 67 | 58 | ||||||||||
LwA to outlet | dBA | 80 | 67 | 70 | 76 | 74 | 76 | 72 | 67 | 57 | ||||||||||
LwA to environment | dBA | 68 | 53 | 58 | 61 | 64 | 62 | 56 | 53 | 47 |
ƞ, [%] | MC | EC | N | VSD | [kW] | [A] | [m3/h] | [Pа] | [RPM] | SR | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
50.6 | А | Static | 57.9 | No | 2.040 | 3.9 | 9690 | 376 | 890 | 1 |
Sizes
|
Technical supportPhohe Customer service. +380 44 406 36 25 | Contact informationUkraine, 08150, Boyarka, st 40 years of October, 36 |