VUT 200 H mini
*modification: replacable filter, summer block
Parameter | Value | Unit | |
---|---|---|---|
Phase | 1 | ˜ | |
Voltage | 220-240 | V | |
Frequency | 50/60 | Hz | |
Maximum fan power | 2pcs. х 58 | W | |
Fan current | 2pcs. х 0.26 | A | |
Total unit power | 116 | W | |
Total unit current | 0.52 | A | |
Maximum air capacity | 200 117,8 55,6 0,0556 3340 | m³/h CFM l/s m³/s l/m | |
RPM | 2500 | min -1 | |
Sound pressure level at 3 m | 24-45 | [dBA] | |
Casing material | aluzinc | ||
Maximum transported air temperature | -25 +50 | оC | |
Insulation | 20 mm, mineral wool | ||
Connected air duct size | 100 | mm | |
Weight | 30 | kg | |
Filter: extract | panel filter G4 | ||
Filter: supply | panel filter G4 | ||
Replaceable filter | SF VUT mini G4* | ||
Summer block | VL VUT mini* | ||
Heat recovery efficiency | 85 | up to % | |
Heat exchanger type | cross-flow | ||
Heat exchanger material | aluminium | ||
Duct connection | horizontal | ||
ЕС- motor | no | ||
Type | air handling units with heat recovery | ||
Heat recovery | yes | ||
SEC Class | C |
Sizes | ∅D | B | B1 | B2 | B3 | H1 | H2 | H3 | L | L1 | L2 |
---|---|---|---|---|---|---|---|---|---|---|---|
mm | 99 | 278 | 200 | 121 | 192 | 431 | 84 | 107 | 699 | 640 | 600 |
Phohe
Customer service.
+380 44 406 36 25
Online form
Send a message center customer support.
Specify the working point (click on the diagram). The operating point is automatically added to the printed version of the page (required to press print button).
Sound-power level | Octave-frequency band [Hz] | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to inlet | dBA | 51 | 29 | 47 | 47 | 34 | 40 | 38 | 30 | 20 | ||||||||||
LwA to outlet | dBA | 59 | 35 | 52 | 54 | 51 | 44 | 44 | 31 | 21 | ||||||||||
LwA to environment | dBA | 30 | 5 | 19 | 29 | 25 | 17 | 14 | 4 | 4 |