Vote

Please evaluate our updated site user friendliness

Keep up with us

RSS Subscribe to blog
Vents.TV

Blog messages

Go to blog

VUT 200 V mini

VUT 200 V mini

Air handling unit in the compact sound- and heat-insulated casing with vertical duct connections. Maximum capacity - 200 m3/h.

Products in this series  (3)

  • VUT 300 V mini

    VUT 300 V mini

    VUT 200 V mini (120/60)

    VUT 200 V mini (120/60)

    VUT 300 V mini (120/60)

    VUT 300 V mini (120/60)

  • SR series (round)

    SR series (round)

  • KOM series

    KOM series

  • Speed controller RS-1-300

    Speed controller RS-1-300

  • SRF series

    SRF series

  • C series

    C series

  • Speed controller RS-1-400

    Speed controller RS-1-400

  • BELIMO TF230/TF24

    BELIMO TF230/TF24

  • CB series

    CB series

  • Speed controller RS-…N (V)

    Speed controller RS-…N (V)

  • BELIMO LF230/LF24

    BELIMO LF230/LF24

  • Speed controller RS-…PS

    Speed controller RS-…PS

*modification: replacable filter, summer block
ParameterValueUnit
Phase
1
˜
Voltage
220-240
V
Frequency
50/60
Hz
Maximum fan power
2pcs. х 58
W
Fan current
2pcs. х 0.26
A
Total unit power
116
W
Total unit current
0.52
A
Maximum air capacity
200
117,8
55,6
0,0556
3340
m³/h
CFM
l/s
m³/s
l/m
RPM
2500
min -1
Sound pressure level at 3 m
24-45
[dBA]
Casing material
aluzinc
Maximum transported air temperature
-25 +50
оC
Insulation
20 mm, mineral wool
Connected air duct size
100
mm
Weight
30
kg
Filter: extract
panel filter G4
Filter: supply
panel filter G4
Replaceable filter
SF VUT mini G4*
Summer block
VL VUT mini*
Heat recovery efficiency
85
up to %
Heat exchanger type
cross-flow
Heat exchanger material
aluminium
Duct connection
vertical
ЕС- motor
no
Type
air handling units with heat recovery
Heat recovery
yes
SEC Class
C
VUT 200 V mini
Sizes∅DBB1B2B3HH1L1L2L3L4L5L6
mm9927820010916945043164060073.5204396529

E-mail

Please, feel free to contact us.

support@vents.ua

Phohe

Customer service.

+380 44 406 36 25

Online form

Send a message center customer support.


By using this form you confirm that you have read and agree with the site condition and terms.
Send

Specify the working point (click on the diagram). The operating point is automatically added to the printed version of the page (required to press print button).

Sound-power level   Octave-frequency band [Hz]
  Hz   General   63   125   250   500   1000   2000   4000   8000
LwA to inlet   dBA 49 26 46 46 35 37 34 31 18
LwA to outlet dBA 58 37 50 54 50 46 46 31 22
LwA to environment dBA 29 5 21 27 27 18 14 0 4