DESCRIPTION |
-
The VUT PW EC air handling units with water heater are the fully-featured ventilation units ensure air filtration, fresh air supply and stale air extract.
-
The heat energy contained in extract air is transferred to supply air through the plate heat exchanger.
-
The units are suitable for integration into various ventilation and air conditioning networks requiring cost-effective solutions and controllable ventilation.
|
-
The integrated EC motors reduce energy demand by half up to three-fold and provide high air flow and low noise level.
-
All the models are compatible with round 160 (150), 200, 250, 315 and 400 mm air ducts.
|
MODIFICATIONS |
CASING |
|
|
FILTER |
|
|
- Supply filter F7 can be supplied with the few models.
|
MOTOR |
|
|
|
HEAT EXCHANGER |
|
|
|
HEATER |
CONTROL AND AUTOMATION |
|
-
The unit includes an integrated automation and a multifunctional control panel with a remote LCD control panel.
-
The delivery set includes a 10 m connecting cable for connection of the unit to the control panel.
-
The freezing protection function is performed by means of the bypass and the heater.
-
In case of a freezing danger according to the temperature sensor readings the bypass damper is opened to let supply air flow through the bypass duct and not come in contact with the heat exchanger.
-
The heater warms up supply air up to the required temperature and meanwhile the heat exchanger is heated by the warm extract air.
-
After the heat exchanger defrosting the bypass damper closes the bypass duct and the air handling unit reverts to the standard operation mode.
|
The VUT PW EC unit incorporates a LCD control panel
with a colour sensor display PU SENS 01.
|
VUT PW EC CONTROL AND PROTECTION FUNCTIONS |
|
Control panel:
- Turning air handling unit on/off, room temperature indication, low-medium-high speed selection.
- Setting week-scheduled operation.
- Supply and exhaust fan speed stage adjustment from 0 up to 100% during the system set-up.
- Maintaining set supply air temperature by means of controlling the circulating pump and heat medium regulating valve of the water mixing unit.
- Heater freezing protection according to the feedback of the temperature sensor at outlet of the heater and of the return heat medium temperature sensor.
|
- Safe fan start/shutdown.
- Return heat medium temperature maintenance during the fan standby;
- Actuating external air dampers.
- Maintaining set indoor or room air temperature.
- Control according to the duct humidity sensor feedback HV1 (special accessory) or according to the humidity sensor in the control panel.
- Filter clogging control by filter timer.
- Ventilation system shutdown on signal from the fire alarm system.
- Cooler connection possibility.
|