VENTS KSB 200
Compact inline sound- and heat-insulated centrifugal fan with back-curved impeller blades. Maximum capacity - 750 m3/h.
- Description
- Characteristics
- Downloads
- Dimensions
- Additional diagrams
- Designation key
Description
Description
APPLICATIONS | |
|
|
DESIGN | |
|
|
MOTOR | |
|
|
SPEED CONTROL | |
|
|
MOUNTING | |
|
|
The fan with electronic temperature and control module (U option)
|
|
|
|
|
|
Control logic of the fan with the electronic temperature and speed control module
|
|
|
|
There are two switch delay patterns for various cases: | |
|
|
Example for temperature sensor delay: | Example for timer delay: |
|
|
|
|
↓ | ↓ |
|
|
↓ | |
|
|
↓ | ↓ |
|
|
↓ | ↓ |
|
|
↓ | |
|
|
↓ | |
|
|
↓ | |
|
|
|
Characteristics
Characteristics
Parameter |
KSB 200 50 Hz |
KSB 200 60 Hz |
Measurement unit |
---|---|---|---|
Phase | 1 | 1 | ˜ |
Voltage | 230 | 230 | V |
Frequency | 50 | 60 | Hz |
Sound pressure level at 3 m distance | 38 | 39 | dBА |
Air capacity | 730 | 750 | m³/h |
Power consumption | 103 | 122 | W |
RPM | 2550 | 2740 | min-1 |
Current | 0.45 | 0.53 | A |
Max. transported air temperature | -25...+55 | -25...+55 | °С |
Protection rating | IP X4 | IP X4 | - |
Duct diameter | 200 | 200 | mm |
Weight | 10 | 10 | kg |
Design | centrifugal | centrifugal | - |
Sound- and heat-insulated casing | yes | yes | - |
Casing material | galvanized steel | galvanized steel | - |
SEC Class | B | B | - |
Duct | for round air ducts | for round air ducts | - |
Type | supply and exhaust | supply and exhaust | - |
Mounting | Inline | Inline | - |
Files archieve
Downloads
Select document type
Dimensions
Characteristics
Parameter | Value | Measurement unit |
---|---|---|
∅D | 199 | mm |
B1 | 368 | mm |
H | 287 | mm |
B | 432 | mm |
L | 588 | mm |
L1 | 506 | mm |
L2 | 480 | mm |
Additional diagrams
Additional diagrams
Sound-power level | Octave-frequency band [Hz] | |||||||||||||||||||
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to inlet | dBA | 52 | 37 | 38 | 45 | 45 | 39 | 39 | 36 | 26 | ||||||||||
LwA to outlet | dBA | 67 | 49 | 46 | 55 | 64 | 59 | 60 | 53 | 41 | ||||||||||
LwA to environment | dBA | 43 | 33 | 35 | 33 | 38 | 25 | 31 | 25 | 25 |
Designation key
Designation key
Series | Spigot diameter | Options |
VENTS KSB | 100; 125; 150; 160; 200; 250; 315 | S: high-powered motor. U: speed controller with an electronic thermostat and a temperature sensor integrated inside an air duct. Temperature-based operation logic. Un: speed controller with an electronic thermostat and a temperature sensor fixed on a 4-meter cable. Temperature-based operation logic. U1: speed controller with an electronic thermostat and a temperature sensor integrated inside an air duct. Timer-based operation logic. U1n: speed controller with an electronic thermostat and a temperature sensor fixed on a 4-meter cable. Timer-based operation logic. U2n: speed controller with an electronic thermostat and a temperature sensor fixed on a 4-meter cable. Temperature-based switching on/off. R1: power cord with a mains plug. P: integrated smooth speed controller. |
Accessories