VCU 2E 140x60

VCU 2E 140x60

Single-inlet scroll-type centrifugal fan with external rotor motor. Maximum capacity - 515 m3/h.

  • SR series (round)

    SR series (round)

  • FB series (round)

    FB series (round)

  • KOM series

    KOM series

  • NKV series (round)

    NKV series (round)

  • NK series (round)

    NK series (round)

  • Speed controller RS-1-300

    Speed controller RS-1-300

  • Single phase speed controller RSA5E-2-P

    Single phase speed controller RSA5E-2-P

  • Speed controller RS-1-400

    Speed controller RS-1-400

  • Single phase speed controller RSA5E-…M

    Single phase speed controller RSA5E-…M

  • FBK series (round)

    FBK series (round)

  • Speed controller RS-…N (V)

    Speed controller RS-…N (V)


ParameterValueUnit
Voltage
230
V
Frequency
50
Hz
Current
0.64
A
Power consumption
148
W
Maximum air capacity
515
303,335
143,17
0,14317
8600,5
m³/h
CFM
l/s
m³/s
l/m
RPM
2820
min -1
Noise level at 3 m
68
[dBA]
Maximum transported air temperature
-25 +45
оC
Protection rating
IP X4
class
Weight
3.5
kg
Number of poles
2
Impeller diameter
140
mm
Impeller width
60
mm
VCU 2E 140x60
Sizes∅DBHH1H2∅dLL1L2MР
mm1402432871259398510775150116

E-mail

Please, feel free to contact us.

support@vents.ua

Phohe

Customer service.

+380 44 406 36 25

Online form

Send a message center customer support.


By using this form you confirm that you have read and agree with the site condition and terms.
Send

Specify the working point (click on the diagram). The operating point is automatically added to the printed version of the page (required to press print button).

Sound-power level   Octave-frequency band [Hz]
  Hz   General   63   125   250   500   1000   2000   4000   8000
LwA to inlet   dBA 60 44 51 50 37 33 31 27 17
LwA to outlet dBA 58 45 53 44 43 38 31 26 19
LwA to environment dBA 50 41 48 44 35 31 24 20 15