PA 03 W4
Compact suspended sound-insulated fan unit. Supplies fresh filtered air to the premise. Water heater is used for the unit operation at low temperatures. Maximum capacity - 3260 m3/h.
*option
Parameter | Value | Unit | |
---|---|---|---|
Phase | 3 | ˜ | |
Voltage | 400 | V | |
Frequency | 50 | Hz | |
Maximum fan power | 1330 | W | |
Fan current | 2.4 | A | |
Total unit power | 1330 | W | |
Total unit current | 2.4 | A | |
Maximum air capacity | 3260 1920,14 906,28 0,90628 54442 | m³/h CFM l/s m³/s l/m | |
RPM | 2730 | min -1 | |
Sound pressure level at 3 m | 57 | [dBA] | |
Casing material | aluzinc | ||
Maximum transported air temperature | -25 +45 | оC | |
Insulation | 50 mm, mineral wool | ||
Filter | G4 (F7) bag type* | ||
Connected air duct size | 600х350 | mm | |
Weight | 94 | kg | |
Number of water (glycol) coil rows | 4 | ||
Heater type | water | ||
Unit size | 03 | ||
Number of rows in water heater | 4-four rows | ||
ЕС- motor | no | ||
Type | supply | ||
Heat recovery | no |
Sizes | B | B1 | B2 | B3 | H | H1 | H2 | L | L1 |
---|---|---|---|---|---|---|---|---|---|
mm | 600 | 620 | 787 | 744 | 350 | 370 | 500 | 1252 | 1212 |
Phohe
Customer service.
+380 44 406 36 25
Online form
Send a message center customer support.
Specify the working point (click on the diagram). The operating point is automatically added to the printed version of the page (required to press print button).
Sound-power level | Octave-frequency band [Hz] | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to inlet | dBA | 71 | 57 | 71 | 66 | 57 | 51 | 50 | 56 | 56 | ||||||||||
LwA to outlet | dBA | 78 | 57 | 70 | 73 | 73 | 70 | 67 | 64 | 53 | ||||||||||
LwA to environment | dBA | 59 | 39 | 58 | 62 | 51 | 44 | 52 | 49 | 46 |