MPA 1800 W
Sound- and heat-insulated ventilation unit. Supplies fresh filtered air to the premise. Water heater is used for the unit operation at low temperatures. Maximum capacity - 1870 m3/h.
Voltage / frequency: |
Products in this series (6)
Parameter | Value | Unit | |
---|---|---|---|
Phase | 1 | ˜ | |
Voltage | 230 | V | |
Frequency | 50 | Hz | |
Maximum fan power | 490 | W | |
Fan current | 2.15 | A | |
Total unit power | 490 | W | |
Total unit current | 2.15 | A | |
Maximum air capacity | 1870 1101,43 519,86 0,51986 31229 | m³/h CFM l/s m³/s l/m | |
RPM | 1100 | min -1 | |
Sound pressure level at 3 m | 40 | [dBA] | |
Casing material | aluzinc | ||
Maximum transported air temperature | -40 +45 | оC | |
Insulation | 25 mm, mineral wool | ||
Filter | G4 | ||
Connected air duct size | 500х250 | mm | |
Weight | 62.5 | kg | |
Number of water (glycol) coil rows | 4 | ||
High-powered motor | no | ||
Heater type | water | ||
ЕС- motor | no | ||
Type | supply | ||
Heat recovery | no |
Sizes | B | B1 | B2 | B3 | H | H1 | H2 | L | L1 |
---|---|---|---|---|---|---|---|---|---|
mm | 500 | 520 | 649 | 600 | 250 | 270 | 480 | 800 | 680 |
Phohe
Customer service.
+380 44 406 36 25
Online form
Send a message center customer support.
Specify the working point (click on the diagram). The operating point is automatically added to the printed version of the page (required to press print button).
Sound-power level | Octave-frequency band [Hz] | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to inlet | dBA | 73 | 78 | 77 | 77 | 67 | 68 | 62 | 63 | 57 | ||||||||||
LwA to outlet | dBA | 75 | 79 | 78 | 74 | 68 | 73 | 66 | 69 | 66 | ||||||||||
LwA to environment | dBA | 51 | 63 | 61 | 54 | 47 | 44 | 40 | 37 | 33 |
Thank your for your time and your wish to improve our site.