NKD 125-1.2-1
Duct heater for supply air postheating with external control. Heater power - 1,2 kW.
Products in this series (8)
Parameter | Value | Unit | |
---|---|---|---|
Minimum air capacity | 66 | m³/h | |
Current | 5.2 | A | |
Power | 1200 | W | |
Weight | 2.1 | kg |
Sizes | ∅D | B | H | L | L1 |
---|---|---|---|---|---|
mm | 124 | 155 | 251 | 306 | 190 |
Phohe
Customer service.
+380 44 406 36 25
Online form
Send a message center customer support.
- Selection method:
- Performance:
- Pressure:
Duty point
- Performance:- -
- Pressure:- -
- Power:- -
- Recovery Efficiency:- -
The NKD heater parameters calculation example:
- It is necessary to select a heater for supply air post-heating to a temperature of +24 °C, provided the temperature downstream of the heat exchanger is +17 °C. Therefore, it is essential to increase temperature by 7 °C. The ventilation system incorporates the VENTS VUT 350 VB EC A19 air handling unit. The rated air capacity is 400 m3/h. Determine the intersection of the post-heating temperature line (+7 °C) and the rated air capacity line (400 m3/h).
- In this case the 1200 W heater capacity provides necessary post-heating (+7 °C). The NKD heater 160-1.2-1 kW with the diameter matching the spigot diameter of the air handling unit VUT 350 VB EC A19 is a suitable model.