TT Silent-M 315
Inline mixed-flow fans in sound and heat-insulated casing. Maximum capacity - 1950 m3/h.
Parameter | Value | Unit | |
---|---|---|---|
Speed | min / max | ||
Phase | 1 | ˜ | |
Voltage | 230 | V | |
Frequency | 50 / 60 | Hz | |
Current | 0.93 / 1.41 | A | |
Power consumption | 213 / 313 | W | |
Maximum air capacity | 1530 / 1950 901,17 / 1148,55 425,34 / 542,1 0,42534 / 0,5421 25551 / 32565 | m³/h CFM l/s m³/s l/m | |
RPM | 1975 / 2545 | min -1 | |
Noise level at 3 m | 36 / 40 | [dBA] | |
Maximum transported air temperature | 60 | оC | |
Protection rating | IP X4 | class | |
Weight | 25 | kg | |
Spigot size | 315 | mm | |
Sound- and heat-insulated casing | yes | ||
SEC Class | - |
Sizes | ∅D | B | B1 | H | L |
---|---|---|---|---|---|
mm | 313 | 432 | 520 | 434 | 780 |
Phohe
Customer service.
+380 44 406 36 25
Online form
Send a message center customer support.
Specify the working point (click on the diagram). The operating point is automatically added to the printed version of the page (required to press print button).
Sound-power level | Octave-frequency band [Hz] | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to inlet | dBA | 69 | 35 | 47 | 62 | 61 | 64 | 67 | 58 | 55 | ||||||||||
LwA to outlet | dBA | 75 | 40 | 53 | 69 | 69 | 70 | 65 | 55 | 51 | ||||||||||
LwA to environment | dBA | 58 | 25 | 32 | 41 | 51 | 55 | 52 | 49 | 37 |
ƞ, [%] | MC | EC | N | VSD | [kW] | [A] | [m3/h] | [Pа] | [RPM] | SR | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
32.4 | А | Static | 48.2 | No | 0.317 | 1.43 | 1112 | 326 | 2320 | 1 |
Thank your for your time and your wish to improve our site.