VKF 4Е 630
Low pressure axial fan in steel casing for vent duct mounting. Maximum capacity - 12100 m3/h.
Voltage / frequency: |
Products in this series (20)
Parameter | Value | Unit | |
---|---|---|---|
Phase | 1 | ˜ | |
Voltage | 220-240 | V | |
Frequency | 50 / 60 | Hz | |
Current | 3.5 / 4.26 | A | |
Power consumption | 750 / 979 | W | |
Maximum air capacity | 11900 / 12100 7009,1 / 7126,9 3308,2 / 3363,8 3,3082 / 3,3638 198730 / 202070 | m³/h CFM l/s m³/s l/m | |
RPM | 1360 / 1625 | min -1 | |
Noise level at 3 m | 75 / 76 | [dBA] | |
Maximum transported air temperature | -30 +60 / -30 +50 | оC | |
Protection rating | IP X4 | class | |
Weight | 20.13 | kg | |
Spigot size | 630 | mm | |
Number of poles | 4 |
Sizes | ∅D | ∅D1 | B | ∅D2 | ∅d | L |
---|---|---|---|---|---|---|
mm | 645 | 674 | 740 | 715 | 12 | 250 |
Phohe
Customer service.
+380 44 406 36 25
Online form
Send a message center customer support.
Specify the working point (click on the diagram). The operating point is automatically added to the printed version of the page (required to press print button).
Sound-power level | Octave-frequency band [Hz] | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to environment | dBA | 77 | 71 | 73 | 72 | 73 | 71 | 70 | 63 | 59 |
ƞ, [%] | MC | EC | N | VSD | [kW] | [A] | [m3/h] | [Pа] | [RPM] | SR | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
37.5 | А | Static | 44.4 | No | 0.800 | 3.76 | 7095 | 149 | 1290 | 1 |
Thank your for your time and your wish to improve our site.