VUT 1000 PW EC

VUT 1000 PW EC

Ceiling mounted Energy saving Air Handling Unit (AHU) in the sound- and heat-insulated casing with the water heater. Maximum capacity - 1000 m3/h.

Products in this series  (3)

  • VUT 600 PW EC

    VUT 600 PW EC

    VUT 2000 PW EC

    VUT 2000 PW EC

    VUT 3000 PW EC

    VUT 3000 PW EC

  • SR series (round)

    SR series (round)

  • KOM series

    KOM series

  • VVG series (round)

    VVG series (round)

  • USWK series

    USWK series

  • SRF series

    SRF series

  • BELIMO TF230/TF24

    BELIMO TF230/TF24

  • KR series (round)

    KR series (round)

  • BELIMO LF230/LF24

    BELIMO LF230/LF24

*modification
ParameterValueUnit
Phase
1
˜
Voltage
220-240
V
Frequency
50/60
Hz
Maximum fan power
400
W
Fan current
2.26
A
Total unit power
400
W
Total unit current
2.26
A
Maximum air capacity
1000
589
278
0,278
16700
m³/h
CFM
l/s
m³/s
l/m
RPM
2780
min -1
Sound pressure level at 3 m
52
[dBA]
Casing material
aluzinc
Maximum transported air temperature
-25 +60
оC
Insulation
20 mm, mineral wool
Connected air duct size
250
mm
Weight
98
kg
Number of water (glycol) coil rows
4
Heater type
water
Filter: extract
G4
Filter: supply
G4 (F7*)
Heat recovery efficiency
90
up to %
Heat exchanger type
counter-flow
Heat exchanger material
polysterene
ЕС- motor
yes
Type
air handling units with heat recovery
Heat recovery
yes
SEC Class
-
VUT 1000 PW EC
Sizes∅DBB1B2B3B4HH1LL1
mm2491350121560843065531714313461395

E-mail

Please, feel free to contact us.

support@vents.ua

Phohe

Customer service.

+380 44 406 36 25

Online form

Send a message center customer support.


By using this form you confirm that you have read and agree with the site condition and terms.
Send

Specify the working point (click on the diagram). The operating point is automatically added to the printed version of the page (required to press print button).

Sound-power level   Octave-frequency band [Hz]
  Hz   General   63   125   250   500   1000   2000   4000   8000
LwA to inlet   dBA 67 68 67 67 66 59 61 61 56
LwA to outlet dBA 69 70 71 68 66 66 64 59 58
LwA to environment dBA 47 58 52 47 53 40 41 35 35