VUT 2000 PW EC
Parameter | Value | Unit | |
---|---|---|---|
Phase | 1 | ˜ | |
Voltage | 220-240 | V | |
Frequency | 50/60 | Hz | |
Maximum fan power | 2pcs. х 420 | W | |
Fan current | 2pcs. х 2.5 | A | |
Total unit power | 840 | W | |
Total unit current | 5 | A | |
Maximum air capacity | 1950 1148,55 542,1 0,5421 32565 | m³/h CFM l/s m³/s l/m | |
RPM | 2920 | min -1 | |
Sound pressure level at 3 m | 58 | [dBA] | |
Casing material | aluzinc | ||
Maximum transported air temperature | -25 +40 | оC | |
Insulation | 25 mm, mineral wool | ||
Connected air duct size | 315 | mm | |
Weight | 194 | kg | |
Number of water (glycol) coil rows | 2 | ||
Heater type | water | ||
Filter: extract | G4 | ||
Filter: supply | G4 | ||
Heat recovery efficiency | 75 | up to % | |
Heat exchanger type | cross-flow | ||
Heat exchanger material | aluminium | ||
ЕС- motor | yes | ||
Type | air handling units with heat recovery | ||
Heat recovery | yes | ||
SEC Class | - |
Sizes | ∅D | B | B2 | B3 | B4 | H | H1 | L | L1 |
---|---|---|---|---|---|---|---|---|---|
mm | 314 | 950 | 405 | 225 | 500 | 761 | 367 | 1400 | 1453 |
Phohe
Customer service.
+380 44 406 36 25
Online form
Send a message center customer support.
Specify the working point (click on the diagram). The operating point is automatically added to the printed version of the page (required to press print button).
Sound-power level | Octave-frequency band [Hz] | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to inlet | dBA | 79 | 80 | 80 | 79 | 71 | 72 | 69 | 64 | 58 | ||||||||||
LwA to outlet | dBA | 81 | 84 | 83 | 79 | 71 | 77 | 71 | 73 | 69 | ||||||||||
LwA to environment | dBA | 56 | 56 | 66 | 59 | 55 | 48 | 44 | 38 | 38 |