VENTS CO2-2
- Description
- Characteristics
- Downloads
- Dimensions
Description
Description
APPLICATION
|
MOUNTING AND POWER SUPPLY
|
Characteristics
Characteristics
Parameter |
CO2-2 |
Measurement unit |
---|---|---|
Power source | 24 VAC (50/60 Hz ± 10 %), 24 VDC/1.6 W Max | - |
Gas analyser | Non-dispersive infrared detector (NDIR) with self-calibration system | - |
CO2 measuring range | 0–2,000 ppm (parts per million) | - |
Accuracy at 25 °C, 2,000 ppm | ±30 ppm + 3 % of reading | - |
Response time | max. 2 min | - |
Warm up time for each turning-on | 2 hours (first time), 2 minutes (operation) | - |
Analogue output | 0–10VDC (default), 4–20mA selectable by jumpers | - |
On/Off output |
1X2A switch load Four set points selectable by jumpers |
- |
Overall dimensions LxWxH | 100x80x30 | mm |
Operating conditions/storage recommendations | 0–50 °C; 0–95 % RH non condensing/0–50 °C | - |
Weight | 0.120 | kg |
Mounting | outdoor mounting | - |