VENTS VUT/VUE 180 P5B EC air handling units with heat recovery
- Description
- Modifications
- Downloads
- Designation key
- Accessories
Description
Description
DESCRIPTION |
CASING |
- The air handling units are the fully featured ventilation units with heat recovery for air filtration, fresh air supply and stale air extract.
|
- The casing is made of expanded polypropylene (EPP) possessing high heat- and sound-insulating properties.
|
FILTER |
FANS |
- Two built-in G4 and F7 filters provide efficient supply air filtration.
- The G4 filter is used for extract air filtration.
|
- Efficient electronically commutated motors with external rotor and impeller with forward curved blades.
- Such motors are the most state-of-the-art energy saving solution.
|
 |
HEAT EXCHANGER |
|
- The VUT 180 P5B EC units are equipped with a counter-flow polystyrene heat exchanger.

|
- The VUE 180 P5B EC units are equipped with an enthalpy counter-flow heat exchanger.

|
BYPASS |
AUTOMATION |
- The VUT/VUE 180 P5B EC A14/A21 units are equipped with a bypass for summer cooling.
FREEZE PROTECTION
- For VUT/VUE 180 P5B EC A14 the freeze protection is realized by means of shutdown the supply fan.
- For VUT/VUE 180 P5B EC A21 the freeze protection is realized by means of turning the preheater on (available as an accessory).
MOUNTING
- The unit is designed for suspended ceiling, wall horizontal or vertical installation using the fixing brackets.
- The mounting position of the unit must provide service access for maintenance and repair.
|
- The VUT/VUE 180 P5B EC A21 units are equipped with integrated control system.
- The A21 controller allows integrating the unit into the Smart Home system or BMS (Building Management Systems).
- The unit is controlled via Wi-Fi by means of the VENTS Home mobile application that must be downloaded.
|
- The VUT/VUE 180 P5B EC A14 units are equipped with integrated control system and the A14 wall-mounted control panel with LED indication.
|
CONTROL AND AUTOMATION |
|
Functions |
A21 |
A14 |
Wi-Fi control via mobile application |
+ |
- |
Control via external wired control panel |
Option (A22)
 |
А14
 |
Wired remote LCD control panel |
|
- |
Control via external wireless control panel |
Option (A22 Wi-Fi)
 |
- |
BMS |
RS-485
Wi-Fi
Ethernet
MODBUS (RTU, TCP)
|
- |
Service Vents Cloud Server |
+ |
- |
Speed selection |
+ |
+ |
Filter replacement indication |
According to filter timer |
According to filter timer |
Alarm indication |
Full alarm description in the mobile application |
Alarm LED indication |
Week scheduled operation |
+ |
- |
Bypass |
Auto |
- |
Manual |
Manual |
Timer |
+ |
- |
Boost mode |
+ |
- |
Fireplace mode |
+ |
- |
Freeze protection |
Cyclic shutdown of supply fan |
Cyclic shutdown of supply fan |
Preheating (option) |
- |
Reheater connection |
Option |
- |
Cooler connection |
Option |
- |
Control of minimum supply air temperature |
+ |
- |
Humidity control |
Option |
Option |
CO2 control |
Option |
Option |
VOC control |
Option |
- |
PM2.5 control |
Option |
- |
Fire detector |
Option |
Option |
* Option. The function is available in case of mounting a respective accessory.
|
UNIT DESIGN |
|
 |
APPLICATION OPTIONS |
|
 |
Designation key
Designation key
Series |
Rated air flow [m³/h] |
Mounting type |
Casing design |
Bypass |
Motor type |
Control |
VUT: ventilation with heat recovery VUE: ventilation with energy recovery |
180 |
P: supended mounting |
5: expanded polypropylene |
B: integrated bypass |
ЕС: synchronous electronically commutated motor |
А14 А21 |