Vote

Are you satisfied with the site speed?

Keep up with us

RSS Subscribe to blog
Vents.TV

Blog messages

Go to blog

VPA 150-6,0-3

VPA 150-6,0-3

Sound- and heat-insulated ventilation unit. Supplies fresh filtered air to the premise. Electric heater is used for the unit operation at low temperatures. Maximum capacity - 425 m3/h.

  • SR series (round)

    SR series (round)

  • KOM series

    KOM series

  • KOM1 series (round)

    KOM1 series (round)

  • SRF series

    SRF series

  • C series

    C series


ParameterValueUnit
Phase
3
˜
Voltage
400
V
Frequency
50
Hz
Maximum fan power
98
W
Electric heater power
6000
W
Electric heater current
8.7
A
Fan current
0.43
A
Number of electrical heating elements
3
Total unit power
6098
W
Total unit current
9.13
A
Maximum air capacity
425
250,325
118,15
0,11815
7097,5
m³/h
CFM
l/s
m³/s
l/m
RPM
2705
min -1
Sound pressure level at 3 m
29
[dBA]
Casing material
aluzinc
Maximum transported air temperature
-25 +55
оC
Insulation
25 mm, mineral wool
Filter
G4
Connected air duct size
150
mm
Weight
50
kg
High-powered motor
no
Heater type
electric
ЕС- motor
no
Type
supply
Heat recovery
no
VPA 150-6,0-3
Sizes∅DBB1HLL1
mm149455496.5438800647

E-mail

Please, feel free to contact us.

support@vents.ua

Phohe

Customer service.

+380 44 406 36 25

Online form

Send a message center customer support.


By using this form you confirm that you have read and agree with the site condition and terms.
Send

Specify the working point (click on the diagram). The operating point is automatically added to the printed version of the page (required to press print button).

Sound-power level   Octave-frequency band [Hz]
  Hz   General   63   125   250   500   1000   2000   4000   8000
LwA to inlet   dBA 65 37 53 63 50 53 53 45 30
LwA to outlet dBA 63 22 43 53 52 57 57 46 36
LwA to environment dBA 41 14 34 39 19 27 19 7 0