VUT R 1500 EH ЕС
Air handling unit in sound- and heat-insulated casing with integrated electric heater. Maximum capacity - 1500 m3/h.
Voltage / frequency: |
Products in this series (4)
*option
Parameter | Value | Unit | |
---|---|---|---|
Phase | 3 | ˜ | |
Voltage | 400 | V | |
Frequency | 50/60 | Hz | |
Maximum fan power | 2 pcs. х 222 | W | |
Electric heater power | 9000 | W | |
Total unit power | 9750 | W | |
Total unit current | 14.1 | A | |
Maximum air capacity | 1500 883,5 417 0,417 25050 | m³/h CFM l/s m³/s l/m | |
RPM | 2000 | min -1 | |
Sound pressure level at 3 m | 62 | [dBA] | |
Casing material | aluzinc | ||
Maximum transported air temperature | -25 +60 | оC | |
Insulation | 25 mm, mineral wool | ||
Connected air duct size | 315 | mm | |
Weight | 175 | kg | |
Filter: extract | G4 | ||
Filter: supply | G4 (F7*) | ||
Heat recovery efficiency | 85 | up to % | |
Heat exchanger type | rotary | ||
Heat exchanger material | aluminium | ||
ЕС- motor | yes | ||
Type | air handling units with heat recovery | ||
Heat recovery | yes | ||
SEC Class | - |
Sizes | ∅D | A | E | F | G | J | H | L |
---|---|---|---|---|---|---|---|---|
mm | 314 | 1430 | 427 | 275 | 460 | 560 | 1010 | 855 |
Phohe
Customer service.
+380 44 406 36 25
Online form
Send a message center customer support.
Specify the working point (click on the diagram). The operating point is automatically added to the printed version of the page (required to press print button).
Calculation of air temperature at heat exchanger outlet:
t = tint+keff*(text - tint) / 100,
Where
tint - intake air temperature 0С,
text - extract air temperature 0С,
keff - heat exchanger efficiency (as per diagram), %
Thank your for your time and your wish to improve our site.