VUT R 700 EH EC

VUT R 700 EH EC
VUT R 700 EH EC
  • The unit is equippedf with a water or electric heater.

Air handling unit in sound- and heat-insulated casing with integrated electric heater. Maximum capacity - 700 m3/h.

Voltage / frequency:

OK

Products in this series  (4)

    • VUT R 400 EH EC

      VUT R 400 EH EC

      Maximum capacity - 400 m3/h.

      VUT R 900 EH EC

      VUT R 900 EH EC

      Maximum capacity - 900 m3/h.

      VUT R 1200 EH ЕС

      VUT R 1200 EH ЕС

      Maximum capacity - 1200 m3/h.

      VUT R 1500 EH ЕС

      VUT R 1500 EH ЕС

      Maximum capacity - 1500 m3/h.

    • SR series (round)

      SR series (round)

    • KOM series

      KOM series

    • VVG series (round)

      VVG series (round)

    • SRF series

      SRF series

    • C series

      C series

    • BELIMO TF230/TF24

      BELIMO TF230/TF24

    • BELIMO LF230/LF24

      BELIMO LF230/LF24

    • KRV series (round)

      KRV series (round)

    *option
    ParameterValueUnit
    Phase
    1
    ˜
    Voltage
    220-240
    V
    Frequency
    50/60
    Hz
    Maximum fan power
    2 pcs. x 105
    W
    Electric heater power
    3300
    W
    Total unit power
    3615
    W
    Total unit current
    15.8
    A
    Maximum air capacity
    700
    412,3
    194,6
    0,1946
    11690
    m³/h
    CFM
    l/s
    m³/s
    l/m
    RPM
    2600
    min -1
    Sound pressure level at 3 m
    52
    [dBA]
    Casing material
    aluzinc
    Maximum transported air temperature
    -25 +60
    оC
    Insulation
    20 mm, mineral wool
    Connected air duct size
    250
    mm
    Weight
    128
    kg
    Filter: extract
    G4
    Filter: supply
    G4 (F7*)
    Heat recovery efficiency
    85
    up to %
    Heat exchanger type
    rotary
    Heat exchanger material
    aluminium
    ЕС- motor
    yes
    Type
    air handling units with heat recovery
    Heat recovery
    yes
    SEC Class
    A
    VUT R 700 EH EC
    Sizes∅DAEFGJHLL1
    mm2491210243180340580700745250

    E-mail

    Please, feel free to contact us.

    support@vents.ua

    Phohe

    Customer service.

    +380 44 406 36 25

    Online form

    Send a message center customer support.


    By using this form you confirm that you have read and agree with the site condition and terms.
    Send

    Specify the working point (click on the diagram). The operating point is automatically added to the printed version of the page (required to press print button).

    Calculation of air temperature at heat exchanger outlet:

    t = tint+keff*(text - tint) / 100,

    Where  

    tint - intake air temperature 0С,      

    text - extract air temperature 0С,    

    keff - heat exchanger efficiency (as per diagram), %