VUT R 900 WH EC
Air handling unit in sound- and heat-insulated casing with integrated water heater. Maximum capacity - 900 m3/h.
Voltage / frequency: |
Products in this series (4)
Parameter | Value | Unit | |
---|---|---|---|
Phase | 1 | ˜ | |
Voltage | 220-240 | V | |
Frequency | 50/60 | Hz | |
Maximum fan power | 2 pcs. x 135 | W | |
Total unit power | 440 | W | |
Total unit current | 1.9 | A | |
Maximum air capacity | 900 530,1 250,2 0,2502 15030 | m³/h CFM l/s m³/s l/m | |
RPM | 2600 | min -1 | |
Sound pressure level at 3 m | 58 | [dBA] | |
Casing material | aluzinc | ||
Maximum transported air temperature | -25 +60 | оC | |
Insulation | 20 mm, mineral wool | ||
Connected air duct size | 250 | mm | |
Weight | 130 | kg | |
Filter: extract | G4 | ||
Filter: supply | G4 (F7*) | ||
Heat recovery efficiency | 85 | up to % | |
Heat exchanger type | rotary | ||
Heat exchanger material | aluminium | ||
ЕС- motor | yes | ||
Type | air handling units with heat recovery | ||
Heat recovery | yes | ||
SEC Class | A |
Sizes | ∅D | A | E | F | G | J | H | L | L1 |
---|---|---|---|---|---|---|---|---|---|
mm | 249 | 1210 | 243 | 180 | 340 | 580 | 700 | 745 | 250 |
Phohe
Customer service.
+380 44 406 36 25
Online form
Send a message center customer support.
Specify the working point (click on the diagram). The operating point is automatically added to the printed version of the page (required to press print button).
Calculation of air temperature at heat exchanger outlet:
t = tint+keff*(text - tint) / 100,
Where
tint - intake air temperature 0С,
text - extract air temperature 0С,
keff - heat exchanger efficiency (as per diagram), %
Calculation of water heater parameters
How to use water heater diagrams:
Air Speed. Starting from 650 m3/h on the air flow scale draw a vertical line 1 till the air speed axis which makes about 2.35 m/s.
- Supply air temperature. Prolong the line 1 up to the point where it crosses the outside air temperature (blue curve), e.g. +5°C; then draw a horizontal line 2 from this point to the left till crossing water in/out temperature curve (70/50 °C). From this point draw a vertical line 3 to the supply air temperature axis on top of the graphic (+26°С).
- Heating coil capacity. Prolong the line 1 up to the point where it crosses the outside air temperature indicated as red curve (e.g., +5°С) and draw a horizontal line 4 from this point to the right to the intersection of water in/out temperature curve (e.g., 70/50 °С). From this point draw a vertical line 5 up to the scale of heating coil capacity (5.8 kW).
- Water flow. Prolong the line 6 down to water flow axis at the bottom of the graphic (0.04 l/s).
- Water pressure drop. Draw the line 7 from the point where line 6 crosses the black curve to the pressure drop axis (0.5 kPa).