Vote

Basic parameter for domestic fan selection

Keep up with us

RSS Subscribe to blog
Vents.TV

Blog messages

Go to blog

VPA 100-1,8-1

VPA 100-1,8-1

Sound- and heat-insulated ventilation unit. Supplies fresh filtered air to the premise. Electric heater is used for the unit operation at low temperatures. Maximum capacity - 190 m3/h.

  • SR series (round)

    SR series (round)

  • KOM series

    KOM series

  • KOM1 series (round)

    KOM1 series (round)

  • SRF series

    SRF series

  • C series

    C series


ParameterValueUnit
Phase
1
˜
Voltage
230
V
Frequency
50
Hz
Maximum fan power
73
W
Electric heater power
1800
W
Electric heater current
7.8
A
Fan current
0.32
A
Number of electrical heating elements
3
Total unit power
1873
W
Total unit current
8.12
A
Maximum air capacity
190
111,91
52,82
0,05282
3173
m³/h
CFM
l/s
m³/s
l/m
RPM
2830
min -1
Sound pressure level at 3 m
27
[dBA]
Casing material
aluzinc
Maximum transported air temperature
-25 +55
оC
Insulation
25 mm, mineral wool
Filter
G4
Connected air duct size
100
mm
Weight
50
kg
High-powered motor
no
Heater type
electric
ЕС- motor
no
Type
supply
Heat recovery
no
VPA 100-1,8-1
Sizes∅DBB1HLL1
mm99382421.5408800647

E-mail

Please, feel free to contact us.

support@vents.ua

Phohe

Customer service.

+380 44 406 36 25

Online form

Send a message center customer support.


By using this form you confirm that you have read and agree with the site condition and terms.
Send

Specify the working point (click on the diagram). The operating point is automatically added to the printed version of the page (required to press print button).

Sound-power level   Octave-frequency band [Hz]
  Hz   General   63   125   250   500   1000   2000   4000   8000
LwA to inlet   dBA 50 30 47 47 35 40 37 28 16
LwA to outlet dBA 58 39 50 56 49 45 42 33 23
LwA to environment dBA 31 5 21 28 24 19 13 4 0