VPA 250-6,0-3
Sound- and heat-insulated ventilation unit. Supplies fresh filtered air to the premise. Electric heater is used for the unit operation at low temperatures. Maximum capacity - 990 m3/h.
Voltage / frequency: |
Products in this series (15)
Parameter | Value | Unit | |
---|---|---|---|
Phase | 3 | ˜ | |
Voltage | 400 | V | |
Frequency | 50 | Hz | |
Maximum fan power | 194 | W | |
Electric heater power | 6000 | W | |
Electric heater current | 8.7 | A | |
Fan current | 0.85 | A | |
Number of electrical heating elements | 3 | ||
Total unit power | 6194 | W | |
Total unit current | 9.55 | A | |
Maximum air capacity | 990 583,11 275,22 0,27522 16533 | m³/h CFM l/s m³/s l/m | |
RPM | 2790 | min -1 | |
Sound pressure level at 3 m | 30 | [dBA] | |
Casing material | aluzinc | ||
Maximum transported air temperature | -25 +50 | оC | |
Insulation | 25 mm, mineral wool | ||
Filter | G4 | ||
Connected air duct size | 250 | mm | |
Weight | 52 | kg | |
High-powered motor | no | ||
Heater type | electric | ||
ЕС- motor | no | ||
Type | supply | ||
Heat recovery | no |
Sizes | ∅D | B | B1 | H | L | L1 |
---|---|---|---|---|---|---|
mm | 249 | 487 | 526.5 | 513 | 835 | 684 |
Phohe
Customer service.
+380 44 406 36 25
Online form
Send a message center customer support.
Specify the working point (click on the diagram). The operating point is automatically added to the printed version of the page (required to press print button).
Sound-power level | Octave-frequency band [Hz] | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to inlet | dBA | 65 | 41 | 54 | 61 | 58 | 63 | 62 | 55 | 43 | ||||||||||
LwA to outlet | dBA | 72 | 42 | 55 | 63 | 63 | 68 | 70 | 60 | 45 | ||||||||||
LwA to environment | dBA | 45 | 15 | 30 | 44 | 39 | 37 | 28 | 23 | 6 |
Thank your for your time and your wish to improve our site.