Vote

Basic parameter for domestic fan selection

Keep up with us

RSS Subscribe to blog
Vents.TV

Blog messages

Go to blog

VPA 315-6,0-3

VPA 315-6,0-3

Sound- and heat-insulated ventilation unit. Supplies fresh filtered air to the premise. Electric heater is used for the unit operation at low temperatures. Maximum capacity - 1190 m3/h.

  • SR series (round)

    SR series (round)

  • KOM series

    KOM series

  • KOM1 series (round)

    KOM1 series (round)

  • SRF series

    SRF series

  • C series

    C series


ParameterValueUnit
Phase
3
˜
Voltage
400
V
Frequency
50
Hz
Maximum fan power
171
W
Electric heater power
6000
W
Electric heater current
8.7
A
Fan current
0.77
A
Number of electrical heating elements
3
Total unit power
6171
W
Total unit current
9.47
A
Maximum air capacity
1190
700,91
330,82
0,33082
19873
m³/h
CFM
l/s
m³/s
l/m
RPM
2600
min -1
Sound pressure level at 3 m
30
[dBA]
Casing material
aluzinc
Maximum transported air temperature
-25 +50
оC
Insulation
25 mm, mineral wool
Filter
G4
Connected air duct size
315
mm
Weight
62
kg
High-powered motor
no
Heater type
electric
ЕС- motor
no
Type
supply
Heat recovery
no
VPA 315-6,0-3
Sizes∅DBB1HLL1
mm314527566.5548900750

E-mail

Please, feel free to contact us.

support@vents.ua

Phohe

Customer service.

+380 44 406 36 25

Online form

Send a message center customer support.


By using this form you confirm that you have read and agree with the site condition and terms.
Send

Specify the working point (click on the diagram). The operating point is automatically added to the printed version of the page (required to press print button).

Sound-power level   Octave-frequency band [Hz]
  Hz   General   63   125   250   500   1000   2000   4000   8000
LwA to inlet   dBA 79 55 69 74 68 71 65 64 62
LwA to outlet dBA 82 55 74 74 77 76 74 70 59
LwA to environment dBA 55 32 44 50 49 46 36 31 24