VKMI 100 Q*
Inline centrifugal fan in heat- and sound-insulated casing. Maximum capacity - 210 m3/h.
* Compliant to the ErP-regulation (EC) 327/2011, the power consumption at optimum efficiency is < 125W.
Parameter | Value | Unit | |
---|---|---|---|
Voltage | 220-240 | V | |
Frequency | 50 | Hz | |
Current | 0.37 | A | |
Power consumption | 60 | W | |
Maximum air capacity | 210 123,69 58,38 0,05838 3507 | m³/h CFM l/s m³/s l/m | |
RPM | 2620 | min -1 | |
Noise level at 3 m | 30 | [dBA] | |
Maximum transported air temperature | -25 +55 | оC | |
Protection rating | IP X4 | class | |
Weight | 8.6 | kg | |
High-powered motor | no | ||
Low-noise design | yes | ||
Sound- and heat-insulated casing | yes | ||
SEC Class | C |
Sizes | A | ∅D | B | H | C | h | c |
---|---|---|---|---|---|---|---|
mm | 580 | 98 | 310 | 310 | 298 | 200 | 200 |
Phohe
Customer service.
+380 44 406 36 25
Online form
Send a message center customer support.
Specify the working point (click on the diagram). The operating point is automatically added to the printed version of the page (required to press print button).
Sound-power level | Octave-frequency band [Hz] | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to inlet | dBA | 64 | 48 | 57 | 57 | 59 | 51 | 47 | 40 | 28 | ||||||||||
LwA to outlet | dBA | 55 | 44 | 53 | 48 | 48 | 43 | 39 | 33 | 27 | ||||||||||
LwA to environment | dBA | 48 | 20 | 18 | 20 | 32 | 36 | 36 | 26 | 15 |
Thank your for your time and your wish to improve our site.