VS 560-4D
Inline centrifugal sound- and heat-insulated duct fans with back-curved impeller blades. Maximum capacity - 11340 m3/h.
Parameter | Value | Unit | |
---|---|---|---|
Phase | 3 | ˜ | |
Voltage | 400 | V | |
Frequency | 50 | Hz | |
Current | 5 | A | |
Power consumption | 2380 | W | |
RPM | 1365 | min -1 | |
Noise level at 3 m | 56 | [dBA] | |
Maximum transported air temperature | -40 +60 | оC | |
Protection rating | IP X4 | class | |
Maximum air flow capacity at cross directed | 11340 | m³/h | |
Maximal air flow capacity at straight directed | 10490 | m³/h | |
Weight | 99 | kg | |
Spigot size | 560 | mm | |
Number of poles | 4 |
Sizes | A |
---|---|
mm | 820 |
Phohe
Customer service.
+380 44 406 36 25
Online form
Send a message center customer support.
- Selection method:
- Performance:
- Pressure:
Duty point
- Performance:- -
- Pressure:- -
- Power:- -
- Recovery Efficiency:- -
Sound-power level | Octave-frequency band [Hz] | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Hz | General | 63 | 125 | 250 | 500 | 1000 | 2000 | 4000 | 8000 | |||||||||||
LwA to inlet | dBA | 80 | 66 | 67 | 73 | 75 | 73 | 69 | 67 | 58 | ||||||||||
LwA to outlet | dBA | 80 | 67 | 71 | 73 | 77 | 74 | 73 | 65 | 61 | ||||||||||
LwA to environment | dBA | 63 | 53 | 55 | 59 | 57 | 60 | 53 | 49 | 41 |