Vote

Please evaluate our updated site user friendliness

Keep up with us

RSS Subscribe to blog
Vents.TV

Blog messages

Go to blog

VENTS KSB series

VENTS KSB series

Compact inline sound- and heat-insulated centrifugal fans with back-curved impeller blades and the air capacity  up to 2150 m3/h. Designed for supply and exhaust ventilation systems for premises with high requirements to noise level. Compatible with Ø 100, 125, 150, 160, 200, 250 and 315 mm round ducts.

Voltage / frequency:

OK

Products in this series (8)

Series   Spigot diameter   Options
VENTS KSB
  100; 125; 150; 160; 200; 250; 315   R - power cord with IEC C14 electric plug;
S - high-powered motor;
M – anti-vibration mount;
U - speed controller with electronic thermostat and temperature sensor integrated into the air duct. Equipped with power cord and IEC C14 electric plug. Temperature-based operation logic;
Un -speed controller with electronic thermostat and external temperature sensor fixed on 4 m cable. Equipped with power cord and IEC C14 electric plug. Temperature-based operation logic;
U1 - speed controller with electronic thermostat and temperature sensor integrated into the air duct. Equipped with power cord and IEC C14 electric plug. Timer-based operation logic;
U1n - speed controller with electronic thermostat and external temperature sensor fixed on 4 m cable. Equipped with power cord and IEC C14 electric plug. Timer-based operation logic.

 

Applications

KSB fan design enables its application in supply and exhaust ventilation systems for the premises with high requirements to noise level and limited mounting space. Provision is made for installation in a premise above the suspended ceiling. Suitable for connection with 100, 125, 150, 160, 200, 250 and 315 mm round ducts.

Design

The fan casing is made of galvanized steel sheet and provided with heat- and sound-insulating material. Round connecting pipes are fitted with rubber seals.

Motor

The centrifugal impeller with back-curved blades is powered by means of 2-pole asynchronous motor with external rotor. The motors are equipped with built-in thermal overheating protection with automatic restart. Motor ball bearings with selective lubricating oil ensure low-noise and maintenance-free fan operation. KSB...M model motor is installed onto the rubber anti-vibration mounts to reduce vibration and noise. Models marked KSB...S are featured with the high-powered motors.

Speed control

Smooth or step speed control with a thyristor or autotransformer speed controller. Several fans may be connected to one speed controller provided that the total power and operating current do not exceed the rated speed controller parameters.

Mounting

The fans are designed for inline mounting inside an air duct of matching air duct diameter, in any point of the ventilation system and at any angle. The fan shall be fixed to a building by means of supports, suspension brackets or fixation brackets in case of flexible connectors application. The fan can be mounted in any position with respect to the air flow direction indicated with a pointer on the fan casing. Access to the fan maintenance shall be provided.

The fan with electronic temperature and control module (U option)

The ideal solution for ventilation of the premises requiring permanent temperature control, i.e. greenhouses. The fan with the electronic temperature and speed control module provides automatic control of the motor speed (air capacity) depending on air temperature in the air duct or in the room.

The fan front panel has the following control knobs:

  • speed control knob for setting the motor speed;
  • thermostat control knob for setting the temperature set point;
  • thermostat indicator light.

The fan is available in two modifications:

  • with the temperature sensor integrated inside the fan air duct (U/U1 option);
  • with the external temperature sensor fixed on the cable, 4 m long (Un / U1n).
Control logic of the fan with the electronic temperature and speed control module

Set the desired air temperature (thermostat set point) by turning the thermostat control knob. Set the required minimum impeller speed (air flow) by turning the speed control knob. The motor switches to maximum speed (maximum air flow) as the temperature reaches and exceeds the set temperature set point. The motor switches to the preset lower speed as the temperature drops down below the temperature set point. To avoid frequent motor speed switches when the air temperature in the duct is equal to the set temperature point, the speed switch delay is activated. There are two switch delay patterns for various cases:

  1. The temperature sensor-based switch delay (U option): the motor switches to higher speed as the air temperature exceeds 2 °C above the set thermostat set point. The motor revers to the preset lower speed as the air temperature drops below the thermostat set point. This pattern is used to keep air temperature to within 2 °C. In this case the motor speed switches are rare.
  2. The timer-based switch delay (U1 option): as the air temperature exceeds the set thermostat set point, the motor switches to higher speed and the switch delay timer is activated for 5 min. The motor reverts to lower speed as the air temperature drops down below the thermostat set point and only after 5 minuts timer countdown. This pattern is used for exact air temperature control. The speed switches for the fan with U1 option are more frequent as compared to the operating logic of the fan with U option, however the minimum operating cycle at one speed is 5 minutes.
Example for temperature sensor delay:
Example for timer delay:

Initial conditions:

  • rated speed is set as 60% of the maximum speed
  • operating threshold is set as 25°С
  • air temperature in the duct is 20°С

Initial conditions:

  • rated speed is set as 60% of the maximum speed
  • operating threshold is set as 25°С
  • air temperature in the duct is 20°С
Fan operates with the rated speed =60% The temperature in the duct rises, reaches 25°C and keeps rising
  • air temperature in the duct rises
Fan operates with the rated speed =60%
Fan switches to the maximum speed =100% and the delay timer switches for 5 minutes on
  • air temperature in the duct reaches 27°С
Fan switches to the speed =100%
  • the temperature in the duct goes down
The fan operates with the maximum speed =100%
  • air temperature in the duct goes down
Fan operates with the speed =100%
  • the temperature in the duct reaches 25°C and keeps going down
  • temperature in the duct reaches 25°C again
Fan switches to the preset rated speed =60%
after the timer stops, the motor switches to the preset rated speed (=60%). After the speed switch the timer switches again for 5 minutes on
 
 
  • the temperature in the duct rises, reaches 25°C and keeps rising
 
  after the timer stops, the motor switches to the maximum speed (=100%). After the speed switch the timer switches again for 5 minutes on.
 
 
  Thus, in timer delay pattern the delay timer activates every time the fan speed changes.
   
   

E-mail

Please, feel free to contact us.

support@vents.ua

Phohe

Customer service.

+380 44 406 36 25

Online form

Send a message center customer support.

By using this form you confirm that you have read and agree with the site condition and terms.
Send
  • SR series (round)

    SR series (round)

  • FB series (round)

    FB series (round)

  • KOM series

    KOM series

  • NKV series (round)

    NKV series (round)

  • NK series (round)

    NK series (round)

  • Speed controller RS-1-300

    Speed controller RS-1-300

  • Single phase speed controller RSA5E-2-P

    Single phase speed controller RSA5E-2-P

  • Speed controller RS-1-400

    Speed controller RS-1-400

  • Single phase speed controller RSA5E-…M

    Single phase speed controller RSA5E-…M

  • FBK series (round)

    FBK series (round)

  • Speed controller RS-…N (V)

    Speed controller RS-…N (V)